Batterywholesale.com: offering over 3,500 replacement batteries and sealed lead acid batteries for all UPS backup systems including APC UPS Belkin UPS, Conext UPS Tripplite UPS, most UPS systems, Amigo electric scooter batteries, Pride Mobility scooter batteries, Alante electric wheelchair batteries, Jazzyelectric wheelchair batteries, ADI Emergency/Exit lighting, Best Emergency/Exit lighting, Duel Lite Emergency/Exit lighting, G.E. Alarm/Security system batteries, HoneywellAlarm/Security system batteries and more, all at wholesale prices, ready for same day shipping.
 
  Specializing In UPS Batteries, Sealed Lead Acid Batteries & Other Batteries Go To My Account | Home Page
Get Batteries
UPS Replacement Batteries
Battery Manufacturers
Characteristics of Constant Voltage Chargers

This information was obtained from the Panasonic Sealed Lead Acid Batteries Technical Handbook, 1998-1999 It applies to most sealed lead acid batteries.

Characteristics of constant voltage chargers Even with the same voltage set-up, charging time varies with output V-I characteristics.


Precautions
1) When adopting charging methods and charging conditions other than those described in the specifications or the brochures, thoroughly check charging/discharging characteristics and life characteristics of the battery in advance. Selection of appropriate methods and conditions of charging is essential for safe use of the battery and for fully utilizing its discharge characteristics.

2) In cyclic use of the battery, use a charger equipped with a charging timer or a charger in which charging time or charge amount is controlled by other means; otherwise, it will be difficult to judge the completion of the charge. Use of a charger as described above is recommended to prevent undercharge or overcharge which may cause deterioration of the battery characteristics.

3) Continue charging the battery for the specified time or until the charge completion lamp, if equipped, indicates completion of charging. Interruption of charging may cause a shortening of service life.

4) Do not recharge the fully charged battery repeatedly, as overcharge may accelerate deterioration of the battery.

5) In cyclic use of the battery, do not continue charging for 24 hours or longer, as it may accelerate deterioration of the battery.

6) In cyclic service of the battery, avoid charging two or more batteries connected in parallel simultaneously: imbalance of charge/discharge amount among the batteries may shorten the life of batteries.

Precautions on charging

Charging Index



BatteryWholesale.com
UPS Batteries, Sealed Lead Acid Batteries, & Other Batteries

40120 Industrial Park Circle || Georgetown, TX 78626
Tel: 512-869-6280 || Toll Free: 800-365-8444 || Fax: 512-863-0620

Contact Information
HACKER SAFE certified sites prevent over 99.9% of hacker crime.
Phone Order Tracking
Your Shopping Cart
Quick Search
Batteries by Products
Battery Wholesale Services
Battery Wholesale
Battery Information
Popular Products
Sunday, May 11th 2008, 6:45PM CST © 2001-2008 BatteryWholesale.com · Terms and Conditions